Maximum size of cables on incoming Shielded disconnectors:-
For special arrangements consult Schneider Electric.
- 800A (type 1000T) - 4 x SC 960mm, 1 x 4C 400mm, 2 x 4C 300mm
- 1600A (type 2000T) - 7 x SC 960mm, 2 x 4C 400mm, 4 x 4C 300mm
- 2400A (type 3000T) - 14 x SC 960mm
For special arrangements consult Schneider Electric.