What is the distance between centers of the 400A & 630A outgoing SAIF fuseways?

Standard 400 & 630A rated SAIF fuseways mounted on the busbars inside feeder pillars and fuse cabinets with a pitch of 120mm between centres.
This distance will increase if large or multiple cables are to be terminated, i.e. more than 1 x 4 core 300mm.

For more details you can refer to page 27 of the SAIF catalogue.