How can we help you today?

Can the iLD RCCBs be used on 230/400Vac 2 phase and N wiring system?

Yes the iLD RCCBs is compliant with 2P+N 230/400V networks.
You must connect neutral terminals (N) and the last two phases (5-6 & 7-8, for test button function)
RCCB Wiring for 2 phase and N wiring systems

The replacement to the above unit is the Acti9 iLD RCCBs. These are also compatible with 2p+N wiring systems. See below link to instruction sheet.

https://download.schneider-electric.com/doc/QGH86351/QGH86351-03.pdf

Schneider Electric UK

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.