Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can a Contactor be fitted on to the outgoing way of an Isobar 4c/Acti9 Isobar Distribution Board?

The Isobar 4c and Acti9 Isobar Distribution Boards outgoing ways are designed to be fitted only with C60H and iC60H MCB's up to 63A and RCBO's up to 45A

Contactor's and other DIN rail devices cannot be fitted.

They should be fitted on a DIN rail in an enclosure above or below the board

In the case of single phase boards, a multiservice single phase distribution board has a DIN rail already fitted next to the outgoing ways for you to use for contactors/time clocks or similar

See Acti9 catalogue (page22) for part numbers on the Multi Service Single Phase Boards

As for a three phase board an extension box with a DIN rail of 17 single pole ways part number is SEA9BNEX034N, or you can find more extension offers on page 55.