Can the 3-pole MCCBs in the ComPacT NSXm offer be used in a single phase system?
Yes, the ComPacT NSXm MCCBs can be used for single phase systems.
Be advised the tripping curves for the NSXm MCCBs are advised if loaded three phase as standard. If loading a single phase system onto them the thermal protection managed by a bimetallic strip will trip slower than when 3 phases are loaded as represented on the curve.
See extract from catalogue:
Be advised the tripping curves for the NSXm MCCBs are advised if loaded three phase as standard. If loading a single phase system onto them the thermal protection managed by a bimetallic strip will trip slower than when 3 phases are loaded as represented on the curve.
See extract from catalogue: