{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Would an I-line panel with 1200 main breaker have GFI protection as standard per NEC requirements?
Issue:
Would an I-line panel with 1200 main breaker have GFI protection as standard per NEC

Product Line:
I-Line Panelboards

Environment:
Products sold in North America

Resolution:
It is required by NEC if panel is 277V, 480V or 480V Delta. It is not required if it is 120-208 volts. In any case the ground fault protection would have to be quoted for factory installation.  Check with the local Distributor or Sales office for selection and quotation.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: