Issue:
Metal legend plates fitting on the 9001 push buttons.
Product Line:
Push Buttons and Operator Interface
Environment:
9001 Type K and SK Push Buttons
Resolution:
The tab on the top has been moved to the bottom. With the old style legend plate the locking thrust washer was not used. When the locking thrust washer was changed to provide grounding, it must always be used. Therefore the tab on the top of the legend plate will not fit with the new locking thrust washer.
Metal legend plates fitting on the 9001 push buttons.
Product Line:
Push Buttons and Operator Interface
Environment:
9001 Type K and SK Push Buttons
Resolution:
The tab on the top has been moved to the bottom. With the old style legend plate the locking thrust washer was not used. When the locking thrust washer was changed to provide grounding, it must always be used. Therefore the tab on the top of the legend plate will not fit with the new locking thrust washer.