{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Is there a 5% limit for the single phase loading on Delta-Delta connected Transformers with 240/120 Center Tapped secondaries?


Issue:
Center tap capacity of a center tapped delta secondary

Product Line:
LV Transformers

Environment:
Applies to Transformers with center tapped delta secondaries by SquareD/Schneider Electric

Cause:
Center tap capacity must be limited based on Transformer design factors

Resolution:

Delta-Delta connected Transformers are intended to supply balanced three-phase loads, such as motors and compressors. Unbalanced loading can cause a circulating current to flow in the windings. This additional current is like a ``hidden`` load with the Transformer windings and can severely de-rate or even overload the Transformer. Adding a Center Tap on the secondary for a combination of a 240V three-phase and 120V single-phase loads can exacerbate the effect in a more severe imbalance.  When applying 240/120V Secondary Three Phase Transformers by SquareD/Schneider Electric, such as those with catalog numbers ending in T6HCT, the amount of the imbalance allowed when using the Center Tap (CT) to feed 120V loads is limited to 5% of the overall rated KVA of the Transformer to help prevent excessive circulating currents.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: