What is difference between Type NL (K-4 rated) or NLP (K-13 rated) Transformers compared to standard Low Voltage Distribution Transformers?
Issue:
K Rating on Low Voltage Transformers
Product Line:
LV Transformers
Environment:
Product sold in North America
Cause:
Harmonic Energy generation in Electrical Systems
Resolution:
SquareD/Schneider Electric`s line of K-rated transformers are designed to minimize the eddy current, or stray losses within the Transformer. It is these eddy/stray losses that are affected by non-linear loads such as computers, fax machines, and other office electronic equipment. A k13 rated transformer will accommodate a higher level of harmonics without exceeding its temperature rating than a k4 rated unit of the same kVA, voltage and temperature class.
K rated Delta Wye units will operate at full load in circuits rich in harmonics without exceeding the temperature rating of their insulation systems. Once the loading goes above 80% of transformer capacity and a high level of harmonics are present, k4 units should be considered to prevent overheating. At loading levels above 90% a k13 unit should be used. The recommendation to use k Factor Transformers for computer loads assumes high harmonics and high loading levels.
K Rating on Low Voltage Transformers
Product Line:
LV Transformers
Environment:
Product sold in North America
Cause:
Harmonic Energy generation in Electrical Systems
Resolution:
SquareD/Schneider Electric`s line of K-rated transformers are designed to minimize the eddy current, or stray losses within the Transformer. It is these eddy/stray losses that are affected by non-linear loads such as computers, fax machines, and other office electronic equipment. A k13 rated transformer will accommodate a higher level of harmonics without exceeding its temperature rating than a k4 rated unit of the same kVA, voltage and temperature class.
K rated Delta Wye units will operate at full load in circuits rich in harmonics without exceeding the temperature rating of their insulation systems. Once the loading goes above 80% of transformer capacity and a high level of harmonics are present, k4 units should be considered to prevent overheating. At loading levels above 90% a k13 unit should be used. The recommendation to use k Factor Transformers for computer loads assumes high harmonics and high loading levels.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.