Can you field adjust or change the phase bus connections on a I-line breaker?

Issue:
Can you field adjust or change the phase bus connections on a I-line breaker?

Product Line:
Bircuit breakers

Environment:
I-line circuit breakers

Cause:
Need CBA configuration

Resolution:
No, the phases are permanently affixed to their phase positions. You need to ask for the right phase configuration on one and two poles breakers . Three pole breakers come as ABC as std and do not have to be identified. If you need CBA then you have to include CBA as part of the part number.