What is the largest breaker that can go on the right side of a HCW I-line interior with LX, LC breakers on the left?
Issue:
On a legacy HCW ILine interior with LX & LC Frame breakers on the Wide side, what is the largest breaker can be installed into the narrow side?

Product Line:
I-line Panelboards

Environment:
Product Features

Resolution:
The KA, KH, KC, and KI frame breakers are the largest breakers that can be mounted on the right side of main bus.