Issue:
What style of cable/wire is recommended for use on Hospital isolation Panels?
Product Line:
Medical Panels
Environment:
Wiring Isolation panels and remote accessories.
Cause:
Due to concerns with leakage currents in Isolated Power Systems, a proper wire can be a way to minimize the extent of it.
Resolution:
A cable with 3.5 dielectrics, such as an XHHW2 cable is recommended.
CTA-ID: 2013772