What is meant by "Momentary Current" ratings of a Medium voltage HVL switch?
Issue:
What is the momentary current rating for our HVL switches?
Product Line:
MV switch
Environment:
HVL
Resolution:
The momentary current is the maximum current a CLOSED switch can withstand for 10 cycles and remain closed without damage to the switch/device. Transformer inrush currents are an example. Momentary currents are expressed in Asymmetrical amperes. 61kA & 80kA are HVL ratings.
What is the momentary current rating for our HVL switches?
Product Line:
MV switch
Environment:
HVL
Resolution:
The momentary current is the maximum current a CLOSED switch can withstand for 10 cycles and remain closed without damage to the switch/device. Transformer inrush currents are an example. Momentary currents are expressed in Asymmetrical amperes. 61kA & 80kA are HVL ratings.
Released for: Schneider Electric USA