Issue:
What enclosures and operators to use for Class 1 Div 2?
Product Line:
30mm Push Buttons
Environment:
Type K and SK Electrical Components
Cause:
Determine is Schneider Electric has an control station to offer for this application.
Resolution:
Yes , but only for Class 1 Division 2 or Class II Division 2 Groups E & F. Any Nema 4 & 13 enclosure ( ie. 9001KY** , KYSS** , SKY*** ) can be used, if hermetically sealed contact blocks ( ie. 9001KA41 , 51 ) are used with 9001K or SK operators ( except potentiometers ) .