Will a PowerPacT H frame with a GFM150HD ground fault module fit into an HCN I-Line panel?
Issue:
GFM150HD ground fault module into an HCN I-Line Panel

Product Line:
Panelboards

Resolution:
No. You must use at least an HCP type panel to fit the GFM module into it, since the module adds 4.85" to the length of the breaker.