How can we help you today?

Can the PowerPact H and J breakers be used on a corner grounded delta system?

Product Line:
Circuit Breakers

Resolution:
Yes, the PowerPact H and J breakers can be used on 3 phase, 3 wire grounded B phase systems.

  • A 2p breaker with the special 1Ø-3Ø marking may be used on a 240 Vac or 480 Vac corner grounded system (see specific breaker label for its particular interrupt rating)
  • A 3p breaker may be used on a 240 Vac or 480 Vac corner grounded system without special marking

See the attached file.

Schneider Electric USA

Attachment(s)
corner gounded.xlsx [98.38 KB]
Corner-Grounded Delta 2700DB0202.pdf [124.08 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings