Are the 8910DPA contactors available with NC contacts? Can the contacts be field converted?

Issue:
8910DPA with NC contacts

Product Line:
Definite Purpose Contactors

Environment:
Types DP, DPA

Resolution:
The 8910`s can come with NC contacts ONLY with 4 pole devices and limited to 8910DPA14, 24, and 34. Also, it needs to have form Y392 for it to have 2NC contact out of the 4 poles. The 8910 DPA contactors cannot be field converted from NO to NC.

Schneider Electric USA