Are individually mounted enclosures available for the PowerPact H and J frame circuit breakers?

Article available in these languages:

  • Spanish

Issue:
What are the available enclosures for Powerpact H and J frame breakers?

Product Line:
Powerpact Breakers

Resolution:
Yes, below are the options for the Powerpact H and J frame enclosures.  Please read all applicable footnotes.
Enclosure table from Digest
  • [9] Rated for 240 Vac maximum. Short circuit current rating is 25 kAIR at 240 Vac.
  • [10] Accepts standard 80% rated circuit breakers only. Not rated for 100% rated circuit breakers.
  • [11] Use copper conductors only.
  • [12] Rated 480 Vac maximum. Short circuit current rating is 18 kAIR at 480 V.
  • [13] For conduit entry through the top end wall use one of the following Square D conduit hubs: A200L for 2.00 in., A250L for 2.50 in., A300L for 3.00 in., A350L for 3.50 in. or A400L for 4.00 in.
  • [14] Add suffix BE if no knockouts are required on the end walls.
  • [15] For access to the circuit breaker’s standard, ammeter or energy trip unit panel/LCD, add suffix T.
  • [16] For 200% neutral use copper wire only.
  • [17] Complete rating is NEMA 3, 3R, 4, 4X, 5, and 12.
  • [18] For NEMA 3R applications, remove drain screw from bottom endwall.
  • [19] Add suffix VW for visibility to the standard, ammeter or energy trip unit of the PowerPact circuit breaker.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings