What is the ground bar for an NQ 54 circuit panelboard? Does the panel require two-ground bars?
Issue:
Selection of ground bar for a 54 circuit NQ panelboard.
Product Line:
NQ Panelboards
Environment:
Typical application.
Cause:
NEC Codes and Standards
Resolution:
The National Electric Code allows for two ground conductors to be terminated in a single port. The 27 port ground bar (PK27GTA) will accept 54 ground conductors.
Selection of ground bar for a 54 circuit NQ panelboard.