What is the ground bar for an NQ 54 circuit panelboard? Does the panel require two-ground bars?
Issue:
Selection of ground bar for a 54 circuit NQ panelboard.

Product Line:
NQ Panelboards

Environment:
Typical application.

Cause:
NEC Codes and Standards

Resolution:
The National Electric Code allows for two ground conductors to be terminated in a single port.  The 27 port ground bar (PK27GTA) will accept 54 ground conductors.