How can we help you today?

What is the ground bar for an NQ 54 circuit panelboard? Does the panel require two-ground bars?

Issue:
Selection of ground bar for a 54 circuit NQ panelboard.

Product Line:
NQ Panelboards

Environment:
Typical application.

Cause:
NEC Codes and Standards

Resolution:
The National Electric Code allows for two ground conductors to be terminated in a single port.  The 27 port ground bar (PK27GTA) will accept 54 ground conductors.

Schneider Electric USA

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings