How to troubleshoot a Micrologic P trip unit that doesn't display voltage or power measurements

Issue:
Micrologic P trip unit doesn't display voltage or power measurements.

Product Line:
PowerPact P and R and Masterpact NT and NW circuit breakers

Resolution:
If this P trip unit was upgraded from either a standard or ammeter trip unit, then to correct this, add the external voltage sensing (EVS) kit. Use:
S64203 for P frame unit mount or I-Line
S64210 for P frame with motor operator or rotary handle
S64209 for P frame drawout
S64208 for R frame unit mount or I-Line
S47506 for fixed NT or NW breakers
S47507 for drawout NT breakers
S48533 for drawout NW breakers
Refer to Installation Bulletin 48049-339-01 for all of the P and R frame kits.
Refer to Installation Bulletin 48049-296-02 for the fixed and drawout NT breakers and 48049-242-02 for the fixed and drawout NW breakers.

Schneider Electric USA

Attachment(s)
EVS P and R frame 48049-339-01[1].pdf [773.47 KB]
EVS NT and NW 48049-296-02[1].pdf [493.53 KB]
EVS NW Drawout 48049-242-02[2].pdf [327.07 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings