Video: What equipment ground kit can be used with the L600AWK and L600AWKMC enclosures and how does it get installed?

Issue:
Application

Product Line:
Circuit Breaker Enclosure

Resolution:
These enclosures use the ground kit PKOGTA4. The PKOGTA4 will accept, PER lug (1) #6 AWG - 250 KCMIL AL or CU ground wires.

The PKOGTA4 comes with 4 Tang Lugs, 1 ground lug mounting bracket and all the mounting hardware and instructions.
The wire binding screws should be torqued to 275 lb-in (31 N-m).

NOTE: MAKE SURE TO VERIFY THE PKOGTA4 KIT CAN BE USED IN THE SPECIFIC CATALOG NUMBER IT IS BEING INSTALLED IN. Because, the PKOGTA4, Service/Equipment grounding lug is used in several different circuit breaker enclosures.
The featured video is ONLY to supplement the INSTRUCTIONS that come with each PKOGTA4 kit.
PLEASE make sure to read and follow the instructions that come with each PK ground kit and all the below Safety Information that is located in the instructions BEFORE working on any electrical equipment.
A PDF of the Instructions for the PKOGTA4, is attached below.
Danger image

Make sure to turn OFF ALL Power supplying the equipment and verify the power is OFF using a properly rated voltage sensing device, BEFORE working on or with electrical equipment.
Once all Safety steps are followed, begin the kit installation by following the instructions that come with the kit.

Schneider Electric USA

Attachment(s)
PKOGTA4 Instructions.pdf [77.71 KB]
Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings