Can you daisy chain ZSI outputs for PowerPacT H, J, and L frame breakers with PowerPacT P and R on the same level?
Issue:
Can you daisy chain H/J/L and P/R/NT/NW trip units together for ZSI?
Product Line:
Molded Case Circuit breakers
Resolution:
Yes, the ZSI outputs of these breakers can be linked together for bringing a common cable to a ZSI interface module, RIM, or upstream PowerPacT/MasterPact breaker.
Can you daisy chain H/J/L and P/R/NT/NW trip units together for ZSI?
Product Line:
Molded Case Circuit breakers
Resolution:
Yes, the ZSI outputs of these breakers can be linked together for bringing a common cable to a ZSI interface module, RIM, or upstream PowerPacT/MasterPact breaker.
Released for: Schneider Electric USA