How can we help you today?

What could cause an ATV61 or ATV71 drive not to start when a run command is present on LI1?

Resolution:

Check the status bar at the top of the display to determine whether the drive is in LOC or REM mode.

  • If the drive is in LOC mode, verify whether any Function Key (F1, F2, F3, or F4) is assigned to T/K. If so, press the assigned key to return the drive to REM mode.

If the drive is already in REM mode, measure the voltage between LI1 and COM (not ground) and verify that approximately 24 VDC is present.

Verify that the drive is configured for terminal control:

  • Drive Menu → 1.6 Command → Cd1 = Terminals

Check the I/O Map to verify that LI1 is being detected by the drive:

  • Drive Menu → 1.2 Monitoring → I/O Map → Logic Inputs Map

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings