Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the definition of peak surge current?
Issue:
"peak surge current" meanning

Product Line:
Surge Protective Devices (SPD's)

Environment:
Products sold and used in North America

Resolution:
The peak ampere surge current ratings of an SPD are typically calculated by adding the peak ampere ratings of the individual suppression components used in a specific protection mode. This includes both line-neutral (L-N) and line-ground (L-G) modes, which are combined to represent a peak ampere rating per phase. For example, L-N 100 kA and L-G 100 kA would provide 200 kA/phase.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings