{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
How to resolve a stop checkback fault on the TeSys T
Issue:
Why does the TeSys T have a stop checkback fault any time an attempt is made to run the motor?

Product Line:
Tesys T Motor Management Systems

Environment:
Tesys T products

Cause:
Programming and Troubleshooting

Resolution:
The stop checkback fault occurs when the motor starts to run without the TeSys T issuing a run command.
This most frequently occurs when the TeSys T is set to independent operating mode but the local operators are wired directly to the contactor, instead of the LTMR block.
If this is causing the issue it can be resolved by changing your operating mode from 2 or 3 wire independent mode over to 2 or 3 wire overload mode.
If the local controls are wired to your TeSys T block you may need to look at what else could be starting your motor.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: