How can we help you today?

What is a start check warning (code 46) on a Tesys T LTMR product?

Issue:
Customer is receiving error 46 Start Check on their Tesys T product.

Product Line:
TeSys T - LTMR

Environment:
US Product

Cause:
Product Specification

Resolution:
Start command check (Error 46) signifies that current is not detected after a delay of 1 second after a start command.  The unit must see a current equal to or more than 10% of FLC minimum.  If the unit is being tested without a motor load, ensure that a current of more than 10% FLC minimum is being passed through the internal CT windows of the device.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings