Is it OK to use a Powerpact or Masterpact breaker with ground fault trip unit on an ungrounded system?
Issue:
Is it OK to use a Powerpact or Masterpact breaker with ground fault trip unit on an ungrounded delta system? Because the system is ungrounded will using a GFI trip unit cause a problem?
Product Line:
Circuit Breakers
Resolution:
There are no negatives (except cost) to applying a Powerpact or Masterpact with integral ground fault protection on an ungrounded delta system. Because the system is ungrounded, a phase to ground contact will not result in current flow to ground and the breaker will not respond. If another phase also had a ground fault, there would be a phase to phase fault through ground which the breaker would respond to as a short circuit if the current was high enough.
The NEC requirements in articles 210.13 and 230.95 are for ground fault protection on solidly grounded WYE systems with 150 V or more to ground, and they say nothing about ungrounded. So our recommendation is to not use breakers with LSIG trip units on ungrounded systems.
Is it OK to use a Powerpact or Masterpact breaker with ground fault trip unit on an ungrounded delta system? Because the system is ungrounded will using a GFI trip unit cause a problem?
Product Line:
Circuit Breakers
Resolution:
There are no negatives (except cost) to applying a Powerpact or Masterpact with integral ground fault protection on an ungrounded delta system. Because the system is ungrounded, a phase to ground contact will not result in current flow to ground and the breaker will not respond. If another phase also had a ground fault, there would be a phase to phase fault through ground which the breaker would respond to as a short circuit if the current was high enough.
The NEC requirements in articles 210.13 and 230.95 are for ground fault protection on solidly grounded WYE systems with 150 V or more to ground, and they say nothing about ungrounded. So our recommendation is to not use breakers with LSIG trip units on ungrounded systems.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.