How do I use the PCFL AIN Function block with Unity Pro / Control Expert
In order to use the PCFL AIN 984LL Function block in Unity Pro you must create a Real data type for the Low Engineering Unit, High Engineering Unit and Scaled output as shown below
The Raw input usually range from 0-4095 (INT)
High Eng unit Word 5 and 6 (Real)
Low Eng unit Word 7 and 8 (Real)
Scaled output Word 13 and 14 (Real)

Summary:
If the raw analog input is 0-4095 and you want this to equate to 25-500 units of something you would enter 25 for Low Engineering Units and 500 for High Engineering Unity and the Output will then be 25 for an analog input of 0 and, 250 for an analog input of 2048 and 500 for 4095.
Attached is a document that outlines how to determine/select the raw analog input range.
The Raw input usually range from 0-4095 (INT)
High Eng unit Word 5 and 6 (Real)
Low Eng unit Word 7 and 8 (Real)
Scaled output Word 13 and 14 (Real)
Summary:
If the raw analog input is 0-4095 and you want this to equate to 25-500 units of something you would enter 25 for Low Engineering Units and 500 for High Engineering Unity and the Output will then be 25 for an analog input of 0 and, 250 for an analog input of 2048 and 500 for 4095.
Attached is a document that outlines how to determine/select the raw analog input range.
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.