What is the Short Circuit Rating For Class 8940 Pump Panels

Issue:
Information on the Class 8940—UL listed Short Circuit Ratings

Product Line:
Contactors and Starters

Environment:
Well-Guard Control™ Pump Panels

Resolution:
See table below.
NEMA SizeNEMA Fuse Class or VoltageEnclosureAvailable Amperes
RMS Symmetrical
Size 0–3Class H or KStandard5,000
Size 0–3Class RStandard100,000
Size 0–2Class H or KStandard5,000
Size 0–2Class RStandard100,000
Size 4-5Class H or KStandard10,000
Size 4-5Class RStandard100,000
Size 6Class H or KStandard18,000
Size 6Class RStandard100,000
Thermal-Magnetic Circuit Breaker Type
Size 0-50-480 VStandard100,000
Size 6-70-480 VStandard65,000
NOTE: Standard enclosures include non-oversize NEMA 1, 4 & 4X Stainless, and 12.