Can ERMS be activated with a physical switch on a Masterpact MTZ breaker?
Issue:
On an MTZ breaker ERMS is normally activated by use of a smart-phone; can it be activated with a physical switch like it was with Masterpact NW?
Product Line:
Circuit Breakers
Resolution:
Yes, it can be activated by installing the ESM module, LV836300SP. It will allow activation and deactivation of ERMS by means of a push button.
The breaker can be ordered with this option from the factory. If not factory installed, it can be field-installed by Schneider Services.
See attached for details.
On an MTZ breaker ERMS is normally activated by use of a smart-phone; can it be activated with a physical switch like it was with Masterpact NW?
Product Line:
Circuit Breakers
Resolution:
Yes, it can be activated by installing the ESM module, LV836300SP. It will allow activation and deactivation of ERMS by means of a push button.
The breaker can be ordered with this option from the factory. If not factory installed, it can be field-installed by Schneider Services.
See attached for details.