How to create an installable library with Control Expert and Unity Pro

Issue
Need to distribute a custom library to other installations of Unity Pro / Control Expert.

Product line
Unity Pro, EcoStruxure Control Expert

Resolution
Expand the custom library folder and from there you can right-click on the individual family folders and select Create Installable Family.

Steps to Create a Custom Library within your installation of Unity Pro / Control Expert
1\ Open a project that has User-created Derived FB Types (i.e. Function Blocks either created in the project by the programmer or imported via .XDB file).
2\ Go to Tools > Types Library Manager
Tools dropdown
3\ Expand the "<Libset V**.*>" node
4\ Right-click the "Custom Lib" folder and choose "Create New Family"
Right-click > Create New Family
5\ Name the folder as desired. I chose "My Custom FB blocks" in the screenshot below.
This folder lives inside the installation of Control Expert on the computer you are working on.
Add a new folder
6\ Once you are satisfied with the creation of a folder, click [Close] to exit the Types Library Manager window
7\ Go back to the Project Browser dockable window and expand the Derived FB Types node with the [+] symbol to the left of the node to expose the Function Block.
8\ Right-click on the name of the FB to bring up the context menu
From the Derived FB Types node Right-click menu, choose Put in Library
9\ Choose "Put in Library"
10\  A popup named "Copy type to library" will appear. In the "Select a Family:" box, choose a folder to save the library into.
Copy type to library
11\ Hit [OK]

The result is that The DFB will now be added to the folder in the Types Library Manager:
DFB now added to the Custom Lib subfolder

Steps on how to share this Library with others:
1\ Click on Tools > Types Library Manager to open the window containing the Custom folder once again.
2\ Right-click on the folder you wish to export and choose "Create Installable Family"
Create Installable Family from Types Library Manager
3\ Enter the path you wish to put the Library into.
If you wish to include sub-types, use the checkbox to do so.
Choose a path
4\ Hit [OK]

Result: The files will be generated in the folder chosen:
Generated folder result

This folder can be moved to a different computer and installed using the "Types Library Update" tool installed as part of the full Control Expert installation.

To Install the Custom Library to a Different Computer
1\ Close all instances of Unity Pro / Control Expert.
2\ Go to the Start Bar and find the "Types Library Update" tool.
Or find the shortcut located here:
Types Library Update tool shortcut location

3\ Enter the path of where you moved the folder in the new computer.
Choose the path of the folder that was moved into the new computer where FAMILY.DSC appears
4\ Click on [Install Family]

Result: The Custom Library will be installed on the PC
Successful install
New folder appears


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance.
Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.