How can we help you today?
Converting Concept READ_REG to Control Expert READ_VAR
Issue
Converting a project from Concept to Control expert and need to understand the pins.
Product line
Unity Pro, Control Expert
Resolution
**Tip, you do not need the Concept help for READ_REG. The READ_REG is supported in Unity Quantum and you can use 'Help on Type' from the block.**
REQ is the trigger for the block. On the READ_VAR, if you enable EN/ENO, this would be the EN pin.
SLAVEREG is the starting register address of the device that you are reading. On the READ_VAR this is the NUM.
NO_REG is the amount or registers. On the READ_VAR this is NB.
ADDRFLD is the port used to send the message and also the slave device IP address. On the READ_VAR it is the ADR pin which gets tied to an ADDM block.
NDR is the success bit. On the READ_VAR it is the least significant bit of the first GEST word. (GEST[0].0)
ERROR is the indication of a bad read. READ_VAR does not have an error bit, you can create one using GEST[1] <> 0. (Second GEST word not equal to 0).
STATUS is the error code. On the READ_VAR it is the second word of the GEST. (GEST[1]).
REG_READ is the data that is returned from the read. In the READ_VAR it is the RECP.
**Define a value other than 0 for the third word of the GEST. This is the timeout field and if the value is left at 0 and the slave device goes down, the block will lock up indefinitely.**
There is a document attached that outlines the GEST management array and includes a breakdown of the error codes.
Here is a link to a video configuring a READ_VAR and M340. https://www.se.com/us/en/faqs/FA213647/
Released for: Schneider Electric USA
Attachment(s)
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.