What does a "triple rating" mean in terms of an industrial control transformers voltage code? Example: 9070T250D1

Issue:
Explain the term triple rating, in terms of an industrial control transformers voltage code.

Product Line:
Transformer

Environment:
class 9070 Industrial Control Transformer

Cause:
Triple rating on Industrial Control Transformers

Resolution:
A triple rating on the control transformer`s voltage code basically means that the transformer is designed to successfully operate at voltages slightly different than the nominal voltage at it`s full VA capacity. This is done to allow for different voltage systems that require the same voltage ratios, say 4:1 or 2:1. Units with triple ratings are clearly marked in the Digest 172 with the triple rating expressed on page 12-13.

Example: The 9070T250D1 is a triple rated voltage code unit that can supply 250VA with the following input voltages and the corresponding output:

Input: 240 or 480
Output: 120

Input: 230 or 460
Output: 115

Input: 220 or 440
Output: 110

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings