What was the maximum ampere rating for the legacy MA frame breaker which could be installed in an I-Line panelboard?

Issue:
legacy MA Characteristics

Product Line:
I-Line Panelboards

Environment:
UL 67, UL 50, CSA C22.2 No.'s 29 & 94-1989, NEMA PB1, NFPA 70 Art. 408, Federal Specification W-P-115C Type 1 Class 1 , 2000 IBC, 1995 NBCC

Cause:
The legacy MA (and related higher AIR frames such as MH, MX, ME) were available in higher ampere ratings; however, these higher ampere ratings were never available with an I-Line jaw for installation in an I-Line panelboard or the I-Line distribution section of a Power-Style or QED2 switchboard.

Resolution:
800A was the maximum ampere rating for an MA frame I-Line branch breaker. This required an HCWM interior. For 900A or 1000A ratings, the legacy NA frame had to be used. The ``N`` frame breaker required an HCWM-U interior (now obsolete) or an HCR-U interior. Both the MA frame and NA frame circuit breakers are now obsolete.  The MA frame is superseded by either the Powerpact M or Powerpact P circuit breaker, according to application details.  The NA frame circuit breaker is superseded by either the Powerpact P or Powerpact R circuit breaker according to application details.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings