What is the wire bending space for an I Line HCR-U Panelboard Interior and Box?

For a Bottom feed panel:

Top (opposite mains) = 12.4``
Bottom (mains end) = 16.3``
Left (wide) side = 11.0``
Right (narrow) side = 5.2``

For TOP Feed application :
Top and Bottom dimensions would be reversed for wire bending dimensions
Wide side gutter dimension would be on the Right side vs Left side as indicated for Bottom feed wire bending dimensions .