What is the part number for replacement 110 / 120 vac control coil for the LC1F400 contactor?

Issue:
LC1F400 replacement coil for 110/120Vac

Product Line:
IEC Contactors and Starters

Environment:
Tesys F Contactors

Resolution:
For standard coil (40 - 400 hertz) order LX1FJ110.

For low sealed consumption coil (40 - 400 hertz) which offers high tolerance to inrush voltage drops, immune to micro-breaks (main supply or contact chain) and are capable of operation on networks with harmonic numbers less than or equal to 7; order LX9FJ925.