Do Emergency Power Generators Require The Use Of Surge Protectors?

Issue:

Are Surge Protectors Needed in Panels using Emergency Power Generators?

Product Line:

Surge Protective Devices

Cause:

Application

Resolution:

For home applications, the event of transferring the home power source from the utility to a generator can create an electrical voltage spike and the generator itself could be a source of spikes and surges. Home emergency generator manufacturers do consider this possibility and most manufacturers include a surge protective device to the output of that generator.

For commercial and industrial applications, No, not every industrial emergency power generator is required to have a surge protector. However, many emergency power systems are required by NEC to include Surge Protective Devices (SPDs) at specific points in the system, and installing them is generally considered a best practice. The code requirement applies to the emergency power distribution equipment rather than the generator alternator itself. However, SPDs are frequently installed:
- At the generator output terminals
- On the generator distribution switchboard
- At the Automatic Transfer Switch (ATS)
- At downstream panels serving sensitive loads
- On control and communication circuits

In both cases, for emergency systems governed by the National Electrical Code (NEC) Article 700, a listed SPD must be installed on emergency system switchboards, switchgear, and panelboards. The requirement is intended to protect life-safety equipment from transient overvoltages caused by lightning, utility switching, generator transfers, and similar events.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.