Does the ATV660 with Full Voltage Bypass have solid state overload protection when in the bypass?

Issue:
Does the Enclosed ATV660 when ordered with Bypass have Solid State Overload?

Resolution:

No. When an Enclosed ATV660 is ordered with the Full Voltage Bypass option, it does not use solid-state overload protection in the bypass circuit.

The bypass package uses two mechanically and electrically interlocked TeSys F contactors to switch the motor between Drive (AFC) mode and Bypass (BYP) mode. Because these are electromechanical contactors, the bypass system is not considered solid-state.

Instead, the enclosure includes a separate Class 20 overload relay that provides motor overload protection while operating in bypass mode.

Features Included with the Bypass Option

  • Class 20 overload protection
  • Overload Trip (yellow) pilot light
  • Bypass (yellow) pilot light
  • Bypass and isolation contactors with mechanical and electrical interlocking
  • Contactor sequencing that provides true motor isolation

ATV660 Manual - https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=NHA91297_02.pdf&p_Doc_Ref=NHA91297

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings