How can we help you today?

What is the replacement bottom plate for an EX transformer with a 25J type enclosure?

Product Line:

Low Voltage EX/EXN Transformer

Environment:

LV Transformer

Cause:

Looking for bottom plate for EX225T3H transformer that is mounted high up, i.e. billboard.

Resolution:

The EX225T3H has a 25J type enclosure. The 25J enclosure is designed to be "Switchboard Style", meaning it mimics our Switchboard Product's open-style bottom access for ease of conduit entry and wire bending, etc. As a result, the open bottom enclosure does not have an option for a bottom plate available at this time. We do not offer any bottom plate for Type 25J enclosure. Since the Transformer is normally placed on a concrete floor or pad, the customer may fabricate a shelf or metal barrier below the Transformer to prevent access to the underside, but any such installation is subject to the discretion of local inspection authorities.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings