Why is it not allowed to use a Q and B-frame as a branch breaker for HCR-U I-Line Main Lugs Interior?

Product Line:

HCR-U I-Line Panelboard

Environment:

I-Line Panelboard

Cause:

Getting an error saying "Main and Feeders, Select a circuit breaker that is not a Q frame or B frame. Main Lug for HCR-U I-LIne is not protected by these circuit breakers".

Resolution:

It has to do with UL series rating testing of the Sub Feed Lug Kits used as Main Lugs on the HCRU interiors. Have to use H or J frame breakers instead.