Issue:
Somove error while downloading a saved file to a VFD
Product Line:
ATV61, ATV71, ATV312, ATV212, ATV12, ATV31, ATV21, ATV32
Environment:
All models and serial numbers
Cause:
Possible issues with downloading Saved Projects to a new VFD.
The drive is of a different type
The drive versions and the file version are not compatible
The drive or drive version is not supported by the version of Somove
The project file is corrupt
There is not an active connection between Somove the VFD
Resolution:
1). Verify the VFD and the version is support by the version of Somove
2). Check that the Project Product Version is the same as the Current Drive Product Version.
3). Verify the comm port setting on the project is the same as the comm port setting being used on the current connection
4). Verify connection to the VFD is possible without downloading a project.
a). Close current project
b). Under File Menu select Go To Start Page
c). Edit Connection and then select the connection type
d). Go to Advanced setting, make the appropriate selection for the connection and press OK
e). Scan Network and wait for somove to scan for devices
f). Select the device to connection
g). Press connect and follow prompt on screen
Somove error while downloading a saved file to a VFD
Product Line:
ATV61, ATV71, ATV312, ATV212, ATV12, ATV31, ATV21, ATV32
Environment:
All models and serial numbers
Cause:
Possible issues with downloading Saved Projects to a new VFD.
The drive is of a different type
The drive versions and the file version are not compatible
The drive or drive version is not supported by the version of Somove
The project file is corrupt
There is not an active connection between Somove the VFD
Resolution:
1). Verify the VFD and the version is support by the version of Somove
2). Check that the Project Product Version is the same as the Current Drive Product Version.
3). Verify the comm port setting on the project is the same as the comm port setting being used on the current connection
4). Verify connection to the VFD is possible without downloading a project.
a). Close current project
b). Under File Menu select Go To Start Page
c). Edit Connection and then select the connection type
d). Go to Advanced setting, make the appropriate selection for the connection and press OK
e). Scan Network and wait for somove to scan for devices
f). Select the device to connection
g). Press connect and follow prompt on screen
Đã phát hành cho: Schneider Electric Việt Nam










Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.