Where do I find the setting for Celsius or Fahrenheit selection within the AP9631 NMC2 Card
Issue:
Unable to find location of the setting for Celsius or Fahrenheit selection for AP9631, RPDU2, and NetBotz 250


Product line:
AP9630
AP9631
AP9635
RPDU2
NBRK0250


Environment:
5.x and 6.x firmware


Resolution:
Log into the NMC card and look at the top right side where you will see the following:

Figure 1

To change for the logged in user, click on the "apc" or currently logged in user option and you will see the following:
Figure 2

Select US Customary for Fahrenheit and Metric (default setting) for Celsius.

To change this setting for all users, Go to configuration --> security --> Local Users --> Default settings.
You will see similar settings options and again select US Customary for Fahrenheit or Metric for Celsius.