1. Launch the Driver Manager. You can locate the driver manager icon in the control panel or from the communication drivers directory under Schneider Electric.
2. select the XWAY text tab.
3. Ensure the following:
driver name= Unitelway
driver instance= 1
remote address= 0.254.0
4. press the "connect" button and the "start" button should highlight
5. Press the start button and you should see the request count incrementing. If the request count increment, you have good communication and if it does not there is a problem with either the driver configuration or you serial port.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.