Issue
Packets captured via Wireshark do not contain the Com'X IP address
Product Line
Com'X 200, Com'X 510
Environment
Wireshark, Com'X gateways
Cause
The Com'X does not transmit its IP address using ARP protocol upon power cycle like the EGX 100/300 gateways.
Resolution
If you are using Windows 7 or Windows Vista, the device should appear as a Network Device.
Details steps are shown in the below video.
Packets captured via Wireshark do not contain the Com'X IP address
Product Line
Com'X 200, Com'X 510
Environment
Wireshark, Com'X gateways
Cause
The Com'X does not transmit its IP address using ARP protocol upon power cycle like the EGX 100/300 gateways.
Resolution
If you are using Windows 7 or Windows Vista, the device should appear as a Network Device.
- Disconnect your computer from all networks (all wired and/or wireless networks).
- Connect an Ethernet cable between your PC (configured as DHCP client) and the Ethernet 2 port on the Com'X.
- Open Windows Explorer and click on Network, the Com'X appears in the list of devices.
- Double-click the Com'X, the login page automatically opens in your browser.
- Type the user name (admin by default) and password (admin by default).
- Then click OK.
- The IP can be found under Settings > General Settings > Network Settings.
Details steps are shown in the below video.
Đã phát hành cho: Schneider Electric Việt Nam




Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.