ATS480 : Why AQ1 is at full scale instead of zero

ATS480 : Why AQ1 is at full scale instead of zero

Goals and symptoms:
Potentially, when AQ1 output is supposed to be zero (0Vdc or 0mA), the AQ1 output value is at full scale (10Vdc or 20mA)

Causes and fixes:
From ATS480 version v1.1IE01, there is a nAQ1 scaling issue.
For some products when AQ1 is at zero, the internal value of AQ1 is negative because of internal AQ1 scaling
Due to this, this internal negative value is considered as a big positive value and the real AQ1 output is set at full scale.

Possible workaround is to set a AQ1 minimum output value
This can be done by adjusting [AQ1 min output] AOL1 or [AQ1 min Output] UOL1 according to [AQ1 Type] AO1T selected
[AQ1 min output] AOL1 = 0,2mA
[AQ1 min Output] UOL1 = 0,1V

This workaround is a temporary solution, the firmware evolution will be provided in a future version

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:

Bạn cần trợ giúp?

Bạn cần trợ giúp?

Công cụ chọn sản phẩm

Công cụ chọn sản phẩm

Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.

Nhận báo giá

Nhận báo giá

Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.

Nơi mua hàng?

Nơi mua hàng?

Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.

Trung tâm Hỗ trợ

Trung tâm Hỗ trợ

Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.

  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cộng đồng Schneider Electric
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings