Cannot see tags in the variable pop up window for HMI service in Web Designer

Issue
Cannot see tags in the variable pop up window for HMI services (i.e., E-mail, Recipedb, ,etc).in web Designer

Product Line
TSX ETG30xx, TSXWMY100, 140NWM100

Environment
Windows 10

Resolution
When you click on the '...' button in the E-mail service for the Web designer application, no tags are shown in the pop up window.

zc c

The reason why the issue is occurring is because the 'Persistence' check box is not selected in the variable tab.
dv vd

To resolve the issue:

  • Open the device variables tab:
sv vs
  • Select the 'checkbox under the column named 'Persistent'.
  • Save the changes.
s vs
  • Double click on the '...' icon to open the 'Variable selection window.
s sv