Which phase current is used for the ANSI 49 (Thermal Overload) thermal replica calculation?

Issue

The thermal overload function is tripping, and the customer wants to verify which current value is used in the thermal model.

Product

MiCOM Series Protection relays

Environment

MiCOM protection relays
ANSI 49 Thermal Overload protection
Current measurement and thermal replica calculation

Cause

Clarification is required regarding how the relay determines the input current for the thermal overload function, especially during unbalanced load or fault conditions.

Resolution

The MiCOM relay family automatically uses the largest phase current among the three phases for the ANSI 49 thermal replica calculation. This ensures worst‑case heating is always considered in the thermal model.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger