What is the replacement for the GV3ME80 thermal-magnetic motor circuit breaker ?
The GV3ME80 has been replaced by the GV3P73 ( setting range 62 ... 73A, motor power at 400/415V: 37kW ).
The GV3P80 is mend for a motor power 45kW / 400/415V only for AC3 ( setting range 70 ... 80A ).
For technical datasheet see attachment.
The GV3P80 is mend for a motor power 45kW / 400/415V only for AC3 ( setting range 70 ... 80A ).
For technical datasheet see attachment.