What coil reference is needed to replace the coil in a LC1F1700P7 TeSys F range contactor?

For the TeSys F contactor LC1F1700P7, the coil is not supplied as a single component. This contactor uses a dual‑coil design, meaning that the replacement requires two identical coil modules.

To replace the coil, you must order:

  • 2 × LX1FK110 coil references

Both coils must be installed together to ensure correct operation of the contactor.

Additional information and recommendations:

  • The LC1F1700P7 is a high‑power TeSys F contactor, and its control system relies on two synchronized coils for proper closing and holding of the contacts.
  • Always replace both coils at the same time, even if only one appears faulty, to maintain balanced performance and avoid uneven wear or malfunction.
  • Ensure the replacement coils have the same control voltage (110 V AC in this case – “P7”) as the original contactor specification.
  • Before installation, isolate the equipment and follow standard safety procedures.
  • After replacement, verify correct wiring and perform a functional test of the contactor.

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings